The MIB, a member of the M II family of economical and highly functional digital protection relays, is a microprocessor based relay that provides three phase high impedance differential protection for Substation Bus-bars of any voltage level.
Use the MIB also to protect electrical machines like transformers, generators or motors against restricted earth faults.
​
Basic protection functions features include a high impedance differential protection unit with a tripping time of 1 1/2 cycles. Stability against external faults is guaranteed thanks to the use of a stabilizing resistor. The unit includes a set of MOVs (Metal Oxide Varistors) provided to clamp the secondary peak voltage below 2kV during fault conditions.
​
The relay includes open CT detection which provides an alarm when it detects sustained current unbalance conditions, issuing a warning signal and blocking the operation of the unit.
​
Features & benefits :
-
Configurable logic, curves, I/Os and LEDs
-
Flash memory for field upgrades
-
Two settings groups
-
Drawout case
-
Password protection for local operation
-
Automatic display of last fault information
-
DC power supply
-
Access via front panel keypad or communication links
-
EnerVista software for setting & monitoring
-
Isolated front RS232 serial port
-
RS485 rear port
Applications
-
Differential protection for single and split busbar arrangements.
-
Zero sequence differential (restricted ground fault) protection for reactors, generators, large motors, and other power apparatus
Protection & Control
-
High impedance differential protection
-
Open CT detection
-
Lockout logic
-
Configurable I/O
-
6 outputs, four configurable, plus trip and alarm
Monitoring & Metering
-
24-event record
-
Analog/digital oscillography
-
Per phase differential current metering
-
Monitoring of the last 5 trips information from the display
User Interface
-
2x16 character LCD display
-
6 LED indicators, 4 configurable in function and color
-
EnerVista software for setting and monitoring
-
Front RS232 and rear RS485 ports using ModBus® RTU protocol up to 19,200 bps
MIB Brochure
MIB Manual